Fire Alarm Systems

     Commercial fire alarm systems are required to be installed by the mandates of local Fire Marshal or Building Inspector. The systems must meet rigid standards set by Federal, State and local agencies. What can a business owner expect to be required?

 

Control Equipment

Control Panel: The control panel must be "commercially rated" by Underwriters Laboratories (UL). It is the "brain" that controls the fire alarm system’s operation. It also must provide a calculated standby battery time in case of power failure.

Display Console: Display consoles are located near the front door of the business or the common lobby, for the purpose of identifying the location of the fire. The responding fire fighters have an indication where to focus their attention.

Initiating Devices
Smoke Detectors: Smoke detectors will be specified throughout the building as per local requirements. The smoke detectors are "zoned" to pinpoint the location of the fire.

Heat Detectors: Heat detectors will be specified in areas that smoke detectors will not perform well, such as a cold unheated warehouse or dusty areas. For attic situations, special 194°F high temperature heat detectors provide protection where temperatures normally reach 150°F on hot summer days. Although they are not as fast-acting as smoke detectors, they provide stable protection.

Duct Detectors: Duct detectors are specifically designed smoke detectors that are installed in the heating and air conditioning ductwork. If a duct detector senses smoke, the duct detector shuts down the building’s heating and air conditioning system to stop the spread of smoke to other areas.
Manual Pull Stations: In order to provide a manual means of signaling the occupants of building a fire, manual pull stations are installed near the exit doors.
 
Notification Devices
Audible Alarm: Horns and Bells generate a system-wide building evacuation signal. Fire Bells have been used in the past extensively, but are now rarely used. Horns have taken their place as the sounder of choice because they emit a special 3-pulse temporal pattern of sound. Eventually, all fire sounders will have this 3-pulse temporal pattern so that the sound is readily identifiable by the public. This will eliminate any confusion to the occupants of a building that the fire alarm has activated, so that they can exit the building quickly.  The audible horn is normally combined with a strobe light for a combination horn/strobe unit.
Strobe Units: The Federal Law "Americans with Disabilities Act" (ADA) requires that hearing impaired persons must have notification of fire. Hence, blinking strobe lights must be installed throughout the building so that hearing impaired persons will have notification of fire.  In ADA constructed bathrooms, a "strobe only" is specified for the benefit of the hearing impaired.  An outdoor strobe light is sometimes required outside the building for the benefit of the responding fire-fighters.
 
Sprinkler Supervision

Sprinkler Water Flow Alarm: Sprinkler valves must be monitored for actual water flow. If a sprinkler head activates, the "water flow valve" will sense the flow of water in the pipe, and the Central Station will respond for a dispatch of the fire department.

Sprinkler Supervisory: A sprinkler supervisory switch should also be installed to detect the accidental or intentional closing of the water supply, or the air pressure drop in dry sprinkler systems.

Wet vs. Dry Systems: Wet sprinkler systems cannot be used in unheated warehouses because the water would freeze in the pipes below 32 degrees Fahrenheit, causing the pipes to burst. Hence, "dry" sprinkler systems are specified that pressurize the pipes with air, holding back the water. If a sprinkler head "pops", the air escapes, and the water enters the pipes permitting the water to flow to extinguish the fire. With a dry sprinkler system, the air pressure must be supervised.
 

Fire Inspections

Fire Inspections: The fire alarm system must be tested periodically according to the schedule prescribed by the local Authority Having Jurisdiction (AHJ). Citadel’s technicians are available to test and inspect the fire alarm, correct any fire system violations, and issue the required certificate.

 

Quick Link:

System Sensor